Brands |
N/A HART® Pyromation® |
Configuration Code |
N/A TM01 |
Transmitter Type |
N/A
Code T142A Description - (4 to 20) mA HART® Field Transmitter with general-purpose aluminum housing Code T142C Description - (4 to 20) mA HART® Field Transmitter with explosionproof aluminum housing; CSA / XP Class I / Div 1/ Groups A,B,C,D / DIP Class II / Div 1 / Groups E,F,G / Class III Code T142E Description - (4 to 20) mA HART® Field Transmitter with flame-proof/ dust-protected aluminum housing; ATEX/IECEx; Ex d IIC T6...T4Gb; Ex tb IIIC T110 ºC Db Code T142F Description - (4 to 20) mA HART® Field Transmitter with general-purpose aluminum housing; IS CSA Class I, Zone 0, AEx ia IIIC T6...T4 Ga EX/AEx ia IIC Ga and NI/NIFW I.S. Class I, Div. 1, Gr. ABCD T6...T4 Class I, Division 2, Groups ABCD; T6...T4 (I.S. Associated Equipment, NIFW for sensor connections) Code T142G Description - (4 to 20) mA HART® Field Transmitter with general-purpose aluminum housing; IS ATEX/IECEx II 1G, II 2G, II 2D Ex ia IIC T6...T4 Ga Ex ia IIC T6...T4 Gb Ex ia IIIC T85...T110 C Db |
Options |
N/A Code B - Bluetooth® (APP) Configuration Code D - Glass Cover with Digital Display Code T - Solid Cover |
Input Type |
N/A Code 00 - Unconfigured (Default setting for unconfigured transmitter is 4-wire Pt100 (0 - 100) ºC.) Code 1 - Thermocouple (TC) or Millivolt Code 2 - Resistance Temperature Detectors (RTD) (2-Wire) Code 3 - Resistance Temperature Detectors (RTD) (3-Wire) Code 4 - Resistance Temperature Detectors (RTD) (4-Wire) |
Sensor Type1 | N/A Code 55 - 500 ohm Platinum (α = 0.003 85 ºC-1) Code 85 - 100 ohm Platinum (α = 0.003 85 ºC-1) Code 95 - 1000 ohm Platinum (α = 0.003 85 ºC-1) Code B - Type B Thermocouple Code E - Type E Thermocouple Code J - Type J Thermocouple Code K - Type K Thermocouple Code Mv - Millivolts Code N - Type N Thermocouple Code R - Type R Thermocouple Code S - Type S Thermocouple Code T - Type T Thermocouple Code W - Resistance |
Failure Mode |
N/A Code D - Downscale Burnout = ≤ 3 mA Code U - Upscale Burnout = ≥ 23 mA |
Range |
N/A Code S - (Lower Limit – Upper Limit) |
Unit of Measure |
N/A Code C - Celsius Code F - Fahrenheit Code K - Kelvin |
Accessories |
N/A Code 10321 - Pipe Mounting Bracket Code 22934 - Replacement Display Board |
Additional Information |
N/A
There is also an optional Bluetooth® configuration. These transmitters are available in General-Purpose or Explosion-Proof aluminum housings.
|